Hyosung

Language

Vacuum Circuit Breaker

Hyosung’s Air Circuit Breaker (ACB) is provided in two standard sizes for optimizing the switchgear.

Downloads
Catalog
Certifications
Search
  • /upload/product/image/1278484878945.jpg

Description

Hyosung’s ACB features eight setting ranges for optimum use on site. It also protects the high current devices by using GE, while the users are protected with ZCT. With two types of standardized external dimension, the design of the switchgear is optimal.

Features

Digitalized OCR for the first time domestically
Accurate measurement and operation enables speedy reactions to accidents
Eight types of settings fine-tuned for the user’s environment
GR not only protects devices but also safeguards human life using ZCT
Variety of choices
630AF, 800AF, 1000AF, 1250AF, 1600AF, 2000AF, 2500AF, 3200AF, 4000AF, 5000AF, 6300AF
Passed the ASTA test, a world-class short circuit test and certification agency
200A 50kA, 1600A, 3200A, 5000A 65kA tests passed in order to obtain international certification
Possess breaking area of a mold type for dual protection of users
A mechanical interlocking input and trip device can be implemented by connecting two or three circuit breakers, installed vertically or horizontally, with a cable
A terminal block of a control circuit can be manually or automatically attached on the front to allow for easy manipulation
Possesses the greatest breaking capability among domestic products of the same class

Specification

Specification/Model SB-606 SB-608 SB-610 SB-612 SB-616
Rated Operational Voltage (VAC) Ue 690 690 690 690 690
Rated Insulation Voltage (VAC) Ui 1,000 1,000 1,000 1,000 1,000
Rated Impulse Withstand Voltage (VAC) Uimp 8,000 8,000 8,000 8,000 8,000
Number of Poles 3P / 4P 3P / 4P 3P / 4P 3P / 4P 3P / 4P
Frame Current (AF) 630 800 1,000 1,250 1,600
Rated Current (A) 630 800 1,000 1,250 1,600
Neutral Phase Current (A) 630 800 1,000 1,250 1,600
Rated
Breaking Capacity
(kA R.M.S. Symmetrical
Breaking duty)
(CO-CO-CO) Icu
IEC
60947-2
VDE 0660
BS 4752
220 / 380V 85 85 85 85 85
440 / 500V 65 65 65 65 65
600V 50 50 50 50 50
690V 42 42 42 42 42
Making Capacity (kA, peak) Icm Less than 500V 143 143 143 143 143
690V 88.2 88.2 88.2 88.2 88.2
Rated Short Time
Withstand Current
(kA) Icw
1sec 65 65 65 65 65
3sec 50 50 50 50 50
Operating Time Total Breaking Time Less than 30ms
Closing Time Less than 30ms
Number of Operating Cycles With Current 5,000 5,000 5,000 5,000 5,000
Without Current 20,000 20,000 20,000 20,000 20,000

Specification

Specification/Model SB-620 SB-625 SB-632 SB-640 SB-650 SB-663
Rated Operational Voltage (VAC) Ue 690 690 690 690 690 690
Rated Operational Voltage (VAC) Ue 1,000 1,000 1,000 1,000 1,000 1,000
Rated Operational Voltage (VAC) Ue 8,000 8,000 8,000 8,000 8,000 8,000
Number of Poles 3P / 4P 3P / 4P 3P / 4P 3P / 4P 3P / 4P 3P / 4P
Frame Current (AF) 2,000 2,500 3,200 4,000 5,000 6,300
Rated Current (A) 2,000 2,500 3,200 4,000 5,000 6,300
Neutral Phase Current (A) 2,000 2,500 3,200 4,000 5,000 6,300
Rated
Breaking Capacity
(kA R.M.S. Symmetrical Breaking duty)
(CO-CO-CO) Icu
IEC 60947-2
VDE 0660
BS 4752
220 / 380V 100 100 100 130 130 130
440 / 500V 85 85 85 100 100 100
600V 65 65 65 85 85 85
690V 50 50 50 65 65 65
Making Capacity (kA, peak) Icm Less than 500V 187 187 187 220 220 220
690V 105 105 105 143 143 143
Making Capacity (kA, peak) Icm 1sec 85 85 85 100 100 100
3sec 65 65 65 85 85 85
Operating Time Total Breaking Time Less than 30ms
Closing Time Less than 70ms
Number of
Operating Cycles
With Current 5,000 5,000 5,000 3,000 3,000 3,000
Without Current 20,000 20,000 20,000 10,000 10,000 10,000
Max.
Weighting (kg)
Drawout Type 3P(4P) 95
(105)
95
(105)
120
(135)
185
(200)
200
(215)
240
(260)
Fixed Type 3P(4P) 48
(63)
48
(63)
55
(70)
100
(115)
120
(135)
145
(155)
Sitemap Legal Notice Privacy Policy